Kanomax
Kanomax Climomaster Series A531, A541, A542, A533, A543
Features
- Probe Compatibility feature allows you to have spare probe.
- The world's most accurate handheld hot-wire anemometer.
- Robust design.
- Detachable probe.
- Automatic Flow Rate Calculation function.
- RS232C terminal for data logging.
- Stores up to 1500 measurement data.
- Differential Pressure available as an option.
- With +/-2% accuracy, there is no match!
- If you have more than one unit, detachable probe allows you to share the main unit or the probe.
- By registering duct sizes (up to 25 duct sizes), it automatically gives you flow rate.
- Well designed software allows you to reach the data instantly.
- You can store the data or you can dump it to your PC via RS232C cable and software.
Kanomax Climomaster Catalog (PDF file)
Kanomax Complete Product Catalog (PDF file)
Kanomax HVAC Solutions Catalog (PDF file)
Kanomax IAQ Solutions Catalog (PDF file)
| Model | A531 | A541 | A542 | A533 | A543 | |
| Standard Probe | A531-01 | A541-01 | A542-01 | A533-01 | A543-01 | |
| Air Velocity | Range | 20 to 6,000fpm (0.10 to 30.0m/s) | 10 to 1,000fpm (0.05 to 5.00m/s) |
|||
| Accuracy | +/-2% of reading or +/-3fpm (+/-0.015m/s) whichever is greater |
|||||
| Response Time | Approx. 1 sec.* | Approx. 4 sec.* | Approx. 7 sec.* | |||
| Resolution | 1 fpm (0.01m/s from 0 to 9.99m/s, 0.1m/s from 10.0 to 30.0m/s) |
1 fpm (0.01m/s) | ||||
| Air Temperature | Range | 32.0 to 140.0F (0.0 to 60.0C) | ||||
| Accuracy | +/- 1F (+/-0.5C) | |||||
| Response Time | Approx. 30 sec.* | |||||
| Resolution | 0.1F (0.1C) | |||||
| Relative Humidity | Range | 2.0 to 98.0%RH | -- | 2.0 to 98.0%RH | -- | |
| Accuracy | +/-2.0%RH from 2 to 80%RH +/-3%RH from 80 to 98%RH |
-- | +/-2.0%RH from 2 to 80%RH +/-3%RH from 80 to 98%RH |
-- | ||
| Response Time | Approx. 15sec. | -- | Approx. 15sec. | -- | ||
| Resolution | 0.1%RH | -- | 0.1%RH | -- | ||
| Differential Pressure (Optional) |
Range | -5.00 to +5.00kPa | ||||
| Accuracy | +/- (3% of reading +0.01)kPa | |||||
| Response Time | Approx. 1 sec. | |||||
| Resolution | 0.01kPa | |||||
| Output | Digital | RS-232c (Baud Rate 4800, 9600, 19200 and 39400bps) | ||||
| Analog | DC0-1V (Select from Air Velocity, Air Temperature, Relative Humidity and Pressure) | |||||
| Power Supply | 6 x 1.5V AA Batteries, AC Adapter (Optional): AC100-240V | |||||
| Battery Life | Approx. 10hrs. Continuous at 984fpm (5m/s), 68F (20C) with alikaline batteries | |||||
| Operating Environment | Main Unit | 41 to 104F (5 to 40C) | ||||
| Probe | 32 to 140F (0 to 60C) | |||||
| Storing Environment | 41-104F (5 to 40C) | |||||
| Weight | Approx. 0.9lbs (400g) | |||||
| Standard Kit | Carrying Case, Operation Manual, AA Batteries, Probe Cable | |||||
| Optional Accessories | Spare Probe, Analog Output, Pressure Sensor, Extension Rod, Printer, Printer Cable, Communication Cable, Software (for Windows), AC Adapter: AC100-240V 50/60Hz | |||||
* at 196fpm (1m/s), 90% response time
| Model | Standard Probe |
| A531 | A531-01 |
| A541 | A541-01 |
| A542 | A542-01 |
| A533 | A533-01 |
| A543 | A543-01 |
| Spare Probe |
Measuring Range | Probe Type | Directivity | Velocity & Temperature |
Relative Humidity |
| A531-01 | 20 - 6,000fpm | Rod | Mono | O | O |
| A541-01 | 20 - 6,000fpm | Rod | Mono | O | x |
| A542-01 | 20 - 6,000fpm | Needle | Omni | O | x |
| A533-01 | 10 - 1,000fpm | Spherical | Omni | O | O |
| A543-01 | 10 - 1,000fpm | Spherical | Omni | O | x |

why buy from us?
We're engineers passionate about home ventilation and serious about customer service – so you can count on us for carefully-selected equipment and expert advice to ensure your project is a success from specification to installation.
Your call is answered by qualified people who will gladly discuss your project in detail, advise you professionally and never sell you inappropriate products.