Setra

Setra 267MR Pressure Transducer

Setra Systems Model 267MR pressure transducers sense gauge (static) or differential pressures and convert this pressure difference to a proportional electrical output. The 267MR offers multi-range capability and field configurable 0-5 VDC or 0-10 VDC output, as well as a 4-20 mA output. There is NO optional LCD display. Used in Building Energy Management Systems, the 267 and 267MR pressure transducers are available for air pressure ranges as low as 0.1 in W.C. (25 Pa) full scale to 30 in. W.C. (7500 Pa) full scale.

Static accuracy is ±1% full scale in normal ambient temperature environments. The units are temperature compensated to less than ±0.06% FS/°C of thermal error over the temperature range of +5 C to +65 C. The 267 series has an IP65/NEMA 4 rated package to withstand environmental effects.

Select From Available Ranges:

Output Options: 4-20 mA Output
0-5 VDC Output
0-10 VDC Output
Elec. Termination Options: PG-13.5 Strain Relief
PG-9 Strain Relief
9 Pin D-Sub Connector
1/2 Inch Conduit Opening
Accuracy Options: Standard 1 % FS Accuracy
1 % FS Accuracy with Certificate
LCD Display Options: No LCD Options Available.
Usually Ships: Limited quantities ship in 1-3 days. Some options may delay shipment, so please call us if you need a rush order.


Model Number:
2671MR1WD11A1CN
 
Product Price (each): $ 178.25 Quantity:
Model 267MR Specifications
Electrical Output, Voltage (Field Selectable)

0 to10 VDC
0 to 5 VDC

Bidirectional Voltage Output at Zero Mid-range of specified output
Electrical Output, Current

4 to 20 mA

Bidirectional Current Output at Zero 12 mA
Accuracy
(RSS Method)
±1.0% FS
Type of Pressure Differential
Pressure Ranges in. W.C.
MR1 = 0 to 0.1, ±0.05
MR2 = 0 to 0.25, 0.5, 1, ±0.125, ±0.25, ±0.5
MR3 = 0 to 1.25, 2.5, 5.0, ±0.625, ±1.25, ±2.5
MR4 = 0 to 7.5, 15, 30, ±3.75, ±7.5, ±15

Pascals
MR5 = 0 to 25, 12.5
MR6 = 0 to 50, 100, 200, ±25, ±50, ±100
MR7 = 0 to 250, 500, 1000, ±125, ±250, ±500
MR8 = 0 to 625, 1250, 2500, ±312, ±625, ±1250
MR9 = 0 to 1875, 3750, 7500, ±937, ±1875, ±3750
Thermal Effects
Compensated Range °F (°C):
+40 to +149 (+5 to +65)
%FS/°F(°C) zero/span shift:
±0.033 (±0.06) zero and span combined
Media Typically air or similar non-conducting gases